SWA Current Carrying Capacity
The current carrying capacity of an SWA cable will depend on the installation method adopted and the application of any relevant correction factors such as grouping or soil resistivity as a couple of examples.
The easiest way to calculate SWA cables is by using our SWA Cable Calculator.
SWA Current Carrying Capacity Tables
SWA current carrying capacity tables are listed in BS 7671, also rating factor tables for various installation methods are listed in Appendix 4 Current Carrying Capacity and Voltage Drop for Cables.
SWA current carrying capacity tables include:
- Single-core armoured 70°C thermoplastic insulated cables (non-magnetic armour)
- Multi-core armoured 70°C thermoplastic insulated cables
- Single-core armoured 90°C thermosetting insulated cables (non-magnetic armour)
- Multi-core armoured 90°C thermosetting insulated cables
16mm SWA Current Carrying Capacity Table:
CSA 15737_2b3b51-44> |
SWA Clipped Direct Current Carrying Capacity (A) 15737_039f75-d5> |
---|---|
1.5 mm² 15737_706fdf-ac> |
23 Amps 15737_0bb292-0b> |
2.5 mm² 15737_eb6a0a-56> |
31 Amps 15737_2e0d3d-26> |
4 mm² 15737_5f9d33-03> |
42 Amps 15737_5ab213-1d> |
6 mm² 15737_4eee64-c5> |
53 Amps 15737_5ae2ad-d1> |
10 mm² 15737_218e92-eb> |
73 Amps 15737_35a893-99> |
16 mm² 15737_4495f0-da> |
94 Amps 15737_96a735-00> |
25 mm² 15737_5306b3-d8> |
124 Amps 15737_228216-6b> |
35 mm² 15737_6dae5e-0f> |
154 Amps 15737_c3169d-1d> |
50 mm² 15737_dd1576-a6> |
187 Amps 15737_7b0bcb-1f> |
70 mm² 15737_a33f59-4b> |
238 Amps 15737_5b2ea9-7d> |
95 mm² 15737_0af4a1-2b> |
289 Amps 15737_41d78d-99> |
120 mm² 15737_4b1855-c1> |
335 Amps 15737_4c7be7-fc> |
150 mm² 15737_3a35b4-af> |
386 Amps 15737_16b767-a2> |
185 mm² 15737_3f87da-8b> |
441 Amps 15737_6345d1-b8> |
240 mm² 15737_8dbf7f-54> |
520 Amps 15737_c833b2-a8> |
300 mm² 15737_6c4014-34> |
599 Amps 15737_d91d68-ae> |
400 mm² 15737_8bccdb-73> |
787 Amps 15737_f9db07-1c> |
SWA Cable Size Current Carrying Capacity

The ccc (current carrying capacity) of an SWA cable is the maximum amount of current the cable can withstand without melting or being subject to damage in normal service.
The maximum current carrying capacity of an SWA cable will depend on many factors, including cable size, number of cores, single phase or three phase and installation reference method.
SWA cables are available in a multitude of sizes and cores varying from 1.5 mm² up to 400 mm² and above. Calculate the required size of an SWA cable which includes current carrying capacity, voltage drop and correction factors.
SWA Cable Size Calculator
Failure to carry out a full and proper SWA cable size calculation may result in an undersized SWA cable being selected, for this, try out our Cable Calculator mobile app. To calculate voltage drop on its own try the voltage drop calculator.
When selecting an SWA cable size, in addition to checking the current carrying capacity of the SWA cable it is also important to check the voltage drop, maximum permissible Zs value of your protective device and apply any relevant correction factors.